Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17362949750

Wuhan GDZX Power Equipment Co., Ltd Hồ sơ công ty
Tin tức
Nhà > Tin tức >
Tin tức về công ty Selection and Application of Power Cable Fault Detection Technologies Under Multiple Operating Conditions--PartI

Selection and Application of Power Cable Fault Detection Technologies Under Multiple Operating Conditions--PartI

2026-06-17
Latest company news about Selection and Application of Power Cable Fault Detection Technologies Under Multiple Operating Conditions--PartI
1: Standards & Test Methods
In-depth Technical Article (Level 1)

Target Readers: Technical engineers, equipment selection personnel, and professionals who need to understand method principles and standard basis.

1. Relevant Standard System

Cable fault testing involves three tiers of standards: equipment manufacturing standards, on-site operation specifications, and acceptance test standards, forming a complete standard system.

1.1 Equipment Standards (Specify technical requirements for testing instruments)
Standard No. Content Status
DL/T 849.1-2019 General Technical Conditions for Special Testing Instruments of Power Equipment Part 1: Cable Fault Flash Tester Valid, implemented in May 2020, replacing the 2004 version
DL/T 849.2 General Technical Conditions for Special Testing Instruments of Power Equipment Part 2: Cable Fault Locator Valid
DL/T 849.3 General Technical Conditions for Special Testing Instruments of Power Equipment Part 3: Cable Path Finder Valid
DL/T 2530.2-2024 General Technical Conditions for Power Cable Testing Equipment Part 2: Cable Sheath Fault Locator Newly issued in 2024; specifies technical requirements for locators adopting step voltage method and pulsating rectangular wave current method
DL/T 846 Series General Technical Conditions for High-Voltage Test Equipment Reference for high-voltage generators
1.2 Operation Specification Standards
Standard No. Content
DL/T 474-2018 Guideline for Field Insulation Tests (including safety operation requirements)
DL/T 1919 Guideline for Condition-based Maintenance of Overhead Lines, Cable Lines and Distribution Facilities in Distribution Network
1.3 Acceptance Test Standards (Criteria for judging qualification after repair)
Standard No. Content
GB/T 50150-2016 Standard for Electrical Equipment Handover Tests of Electrical Installation Engineering
IEC 60502 Series Power Cables with Extruded Insulation and their Accessories for Rated Voltages from 1 kV to 30 kV (International Reference)
IEC 60840 Test Methods for Cables with Rated Voltage above 30 kV (International Reference)

Usage Tip: Standards are continuously updated. Please refer to the current valid version published on the official website of the Standardization Administration of China when citing.

2. Low Voltage Pulse Method (TDR)
2.1 Principle

Time Domain Reflectometry (TDR). A low-voltage narrow pulse is injected into the cable. The pulse propagates along the cable and reflects at positions with impedance mutation. The instrument calculates the fault distance by measuring the time difference.

2.2 Core Formula

Fault distance: S=V×Δt÷2

  • V: Wave propagation velocity in cable (m/μs), varying with cable insulation materials
  • Δt:ime difference between transmitted pulse and reflected pulse (μs)
  • Divided by 2: The pulse travels a round trip, and the measured time is the round-trip duration
2.3 Reference Wave Velocity of Common Cables (Calibration by actual measurement is required, not for direct application)
Insulation Type Reference Wave Velocity Impact of Wave Velocity Deviation
Paper Insulated Lead Covered Cable (PILC) ~160 m/μs A 5% deviation causes a 50 m error for a 1000 m cable
Cross-linked Polyethylene (XLPE) ~170 m/μs Same as above
Ethylene Propylene Rubber (EPR) 150-165 m/μs Large differences among formulas; actual measurement is required
2.4 Waveform Polarity Rules
Fault Type Transmitted Wave Reflected Wave Rule Summary
Open Circuit / Broken Cable Positive Positive Same polarity for open circuit
Low-resistance Short Circuit (R ≤ 100 Ω) Positive Negative Opposite polarity for short circuit
Pure Short Circuit (Impulse Flash Method) Positive Positive Same as open circuit
2.5 Cursor Position Setting
  • Start point: Intersection of rising edge of transmitted pulse and baseline
  • End point (Open circuit): Intersection of rising edge of reflected pulse and baseline
  • End point (Short circuit): Intersection of initial rising edge of reflected pulse and baseline
2.6 Sampling Frequency & Resolution (Default: 25 MHz)

Distance per sampling point: S=V÷(2×f)

  • PILC cable: (160 ÷ (2 *25) = 3.2m/point
  • XLPE cable: (170÷(2 *25) = 3.4) m/point
2.7 Application Scope

✅ Open circuit / broken cable faults

✅ Low-resistance short circuit ((R ≤ 100) Ω)

✅ Measure total cable length (for wave velocity calibration)

✅ Locate cable joints, T-joints and branch points

2.8 Advantages
  • Simple operation and low learning cost
  • No high-voltage equipment required, high safety
  • High ranging accuracy and clear, intuitive waveforms
  • Capable of locating common joints, T-joints and branches simultaneously
2.9 Limitations
  • Only applicable to low-resistance faults (R ≤ 100 Ω)
  • For high-resistance faults, the reflection coefficient approaches zero, and the reflected waveform cannot be identified
  • Unable to directly detect high-resistance leakage faults, which account for about 80% of all cable faults
3. High-Voltage Flashover Method (Pulse Current Method / Impulse Flash Method)
3.1 Principle

High-resistance faults maintain high impedance under low voltage, so low-voltage pulses cannot generate effective reflection. The impulse flash method applies high-voltage impulse to break down the fault point into an instantaneous electric arc (short-circuit state, lasting for tens of milliseconds). The traveling wave of pulse current is collected at this moment to obtain a clear reflected waveform similar to low-resistance short circuit.

3.2 System Wiring

220 V Mains → Voltage Regulator → High-Voltage Transformer → Energy Storage Capacitor → Discharge Gap → Fault Cable

Current Sampler → Test Host (Waveform Acquisition)

3.3 Standard Impulse Flash Waveform (Current Sampling)

Key waveform features: Transmitted pulse, reflected pulse and negative reverse impulse.

  • Start point: Intersection of rising edge of transmitted pulse and baseline
  • End point: Intersection of falling front edge of negative reverse impulse and baseline (set at rising edge if no negative reverse impulse exists)
3.4 Secondary Breakdown Discharge (Special Case)

For individual high-resistance faults, the impulse voltage passes through the fault point to the cable terminal, and flashover is triggered after voltage superposition during the return trip. The waveform presents a two-section structure.

Reading rule: Take the distance of the second section as the actual fault distance.

3.5 Troubleshooting for Non-discharging Fault Points
Step Operation
Step 1 Appropriately widen the discharge gap to increase the threshold of impulse voltage
Step 2 Increase the capacity of energy storage capacitor to boost single impulse energy
Step 3 Apply continuous impulse for a long time to force the fault point to form a stable discharge channel
3.6 Application Scope

✅ High-resistance leakage faults ((R > 100) Ω)

✅ High-resistance flashover faults

✅ Wet joint faults

✅ Faults causing tripping during operation with unobvious symptoms in low-voltage tests

3.7 Advantages
  • Applicable to about 80% of high-resistance leakage faults with strong on-site versatility
  • No need for precise classification of fault types, high fault tolerance
3.8 Limitations
  • High-voltage equipment is required with strict safety operation requirements
  • The amplitude of negative reverse impulse varies with fault properties, and waveform interpretation requires experience
  • Lower accuracy for low-resistance faults than low-voltage pulse method (discharge delay leads to larger ranging error)
  • Complex wiring and numerous operation steps
4. Secondary Pulse Method
4.1 Principle

A combination of low-voltage pulse method (high accuracy but invalid for high-resistance faults) and impulse flash method (applicable to high-resistance faults but complex waveforms):

  1. Transmit low-voltage pulses and record the reference waveform (no reflection at high-resistance fault point)
  2. Apply high-voltage impulse to break down the fault point and form an electric arc
  3. Transmit low-voltage pulses synchronously while the electric arc is burning. The fault point is equivalent to a low-resistance point, generating clear short-circuit reflection
  4. Compare the two waveforms; the difference position is the fault point

This method uses clear waveforms of low-voltage pulse to realize positioning of high-resistance faults.

4.2 Comparison between Pulse Current Method and Secondary Pulse Method
Comparison Item Pulse Current Method (Impulse Flash) Secondary Pulse Method
Waveform Clarity Disturbed by negative reverse impulse; interpretation requires experience Similar to low-voltage pulse, intuitive to read
Applicable Faults High-resistance leakage / flashover faults High-resistance leakage faults (preferred)
Ranging Accuracy Medium Relatively high
Operation Difficulty Need to identify negative reverse impulse Relatively easy
Equipment Requirement High-voltage equipment High-voltage equipment + higher synchronization requirement
4.3 Application Scope

✅ High-resistance leakage faults (higher accuracy than impulse flash method)

✅ Operators with insufficient experience (easy waveform interpretation)

✅ Scenarios requiring reliable ranging results

5. Acoustic-Magnetic Synchronous Positioning Method

Note: This is a positioning method, not a ranging method. It is used for precise ground positioning after rough ranging.

5.1 Working Principle

Apply high-voltage impulse to the fault cable. Discharge at the fault point generates two signals:

  1. Acoustic signal: Discharge energy is converted into mechanical vibration and propagates to the ground through soil or concrete
  2. Electromagnetic signal: Discharge current generates magnetic pulses and radiates to the ground

Ground sensors receive both signals simultaneously. When the sensor is directly above the fault point, the propagation path difference between acoustic and electromagnetic signals is the smallest, and the time difference approaches zero.

Positioning Rule: Move the sensor to find the position with the minimum time difference (close to 0).

5.2 Operation Key Points
  • Move the sensor slowly near the rough ranging range along the confirmed cable path
  • Do not judge only by the maximum sound volume; sound may be reflected by pipelines, manhole covers and joint structures to form false maximum values
  • Repeat tests 2 to 3 times at the same position to confirm stable time difference
  • Verify with cable path and rough ranging distance
5.3 Interference Sources & Solutions
Interference Source Impact Solution
Ground pipelines Sound propagates along pipelines and forms false maximum values Judge by time difference instead of sound volume only
Joint wells & manhole covers Sound propagation path changes in cavities Attach sensor closely to the ground and stay away from manhole covers
Closed faults (sheath faults) Extremely weak discharge sound Increase impulse voltage or adopt professional sheath positioning methods
Road noise Background noise masks discharge sound Avoid rush hours and turn on noise reduction mode
5.4 Applicable & Inapplicable Scenarios
Fault Type Applicability Reason
High-resistance leakage / flashover faults ✅ Most applicable Obvious discharge sound
Low-resistance short circuit ❌ Not applicable No discharge sound; adopt audio induction method instead
Single-core sheath faults (closed type) ⚌ Difficult Extremely weak sound in sealed structure
6. Step Voltage Method (Dedicated for Sheath Faults)
6.1 Reason for Dedicated Sheath Fault Test Methods

The loop of single-core high-voltage cable sheath fault consists of metal sheath, fault point and earth. Pulse signals attenuate severely due to the high attenuation coefficient of earth, so conventional pulse methods have an extremely limited effective ranging range and cannot realize effective positioning.

6.2 Ranging: Bridge Method

Based on Wheatstone bridge principle, calculate fault distance by measuring the resistance ratio between the faulty phase and healthy phase (or auxiliary wire). This method does not rely on pulse reflection and is immune to earth attenuation.

6.3 Positioning: Step Voltage Method

Apply DC or pulsating signal between sheath and earth, and measure the potential difference (step voltage) between two adjacent points on the ground. Abnormal change of step voltage near the damaged sheath indicates the direction and position of the fault point.

6.4 Standard Basis

DL/T 2530.2-2024 General Technical Conditions for Power Cable Testing Equipment Part 2: Cable Sheath Fault Locator, newly issued in 2024, specifies technical requirements, test methods and inspection rules for locators adopting step voltage method and pulsating rectangular wave current method.

6.5 Difficulties in Sheath Fault Positioning

Sheath faults are usually closed faults with extremely weak discharge sound, so acoustic-magnetic synchronous method has poor effect. Professional sheath fault locators are required, and high operational experience is needed.

7. Selection Decision Table for Five Test Methods
Fault Type Recommended Ranging Method Recommended Positioning Method
Open circuit / Broken cable Low-voltage pulse method Acoustic detection method / Audio induction method
Low-resistance short circuit (≤100 Ω) Low-voltage pulse method (priority for accuracy) Audio induction method / Acoustic detection method
High-resistance leakage (>100 Ω) Secondary pulse method (preferred) / Impulse flash method (alternative) Acoustic-magnetic synchronous positioning method
Flashover faults Direct flash method (if conditions permit) / Impulse flash method (after conversion) Acoustic-magnetic synchronous positioning method
Sheath faults Bridge method Step voltage method

Notes: All cited standards are valid versions at the time of compilation. Verify the current status of standards before use. Strictly comply with DL/T 474-2018 and relevant safety regulations during high-voltage tests.

Sự kiện
Liên lạc
Liên lạc: Mrs. Annie
Fax: 86-27-65526007
Liên hệ ngay bây giờ
Gửi cho chúng tôi.